AHU Engineering Report

Air Handling Unit — Full ASHRAE Compliance Analysis

ASHRAE 62.1-2022 ASHRAE 90.1-2022 HoF 2021 Ch.26 ISO 16890
📋Project Information General
🌤Outdoor Design Conditions ASHRAE 169-2021 Climate Data
P_atm = 101.325 · (1 − 2.25577×10⁻⁵ · z)^5.2559 [kPa]
→ z = 500 m → P = — kPa
📖 ASHRAE Fund. 2021 Ch.1 Eq.3
☀ Summer Design — 1% Exceedance
❄ Winter Design — 99.6% Exceedance
☀ Summer OA — Auto Calc
P_atmkPa
Dew Point T_d°C
❄ Winter OA — Auto Calc
P_atmkPa
Dew Point T_d°C
🏢Indoor Design Conditions ASHRAE 55-2020 / 62.1-2022
☀ Summer Set-Point
❄ Winter Set-Point
💨Airflow — Ventilation Rate Procedure ASHRAE 62.1-2022 §6.2
V_bz = R_p·P_z + R_a·A_z [L/s] → V_oa,min = V_bz/1000·3600 [m³/h]
→ V_bz = —
📖 ASHRAE 62.1-2022 §6.2.2 Table 6-1
ASHRAE 62.1 OA Adequacy — V_bz = m³/h
🏭AHU System Schematic System Overview

Air flow path: Outdoor Air → Filters → Crossflow HEX → Coils → Supply Fan → Supply Air
Return path: Exhaust Air → Crossflow HEX → Exhaust Fan → Outside

OUTDOOR AIR SUPPLY AIR G4 Filter F7 Filter CROSSFLOW PLATE HEX ε_s —% ↑ Exhaust ↓ OA Supply COOLING COIL CHW 6/12°C HEATING COIL HHW 80/60°C FAN Supply EXHAUST OUT RETURN AIR EXH FAN ΔP 40+75 Pa SHR= Q=kW SFP=
📊Psychrometric Analysis ASHRAE Fund. 2021, Ch.1
P_ws = 0.61078·exp(17.269T/(237.3+T)) [kPa]
Buck 1981 — Summer: — | Winter: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.6
W = 0.621945·φ·P_ws / (P − φ·P_ws) [kg/kg]
Summer: — | Winter: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.20
h = 1.006·T + W·(2501 + 1.86·T) [kJ/kg_da]
Summer: — | Winter: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.32
ρ = 1/v v = 0.287055·(T+273)·(1+1.608W)/P
Summer ρ: — | Winter ρ: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.28
📊 Psychrometric Chart (SI) — State Points & Processes P_site = kPa
① OA Summer ② OA Winter ③ After HEX (Summer) ④ After HEX (Winter) ⑤ Supply Air / After Coil ⑥ Room / Exhaust
☀ Summer — Outdoor Air
T_db°C
P_wskPa
Wkg/kg_da
hkJ/kg_da
ρkg/m³
T_dew°C
AHg/m³
ṁ_supplykg/s
❄ Winter — Outdoor Air
T_db°C
P_wskPa
Wkg/kg_da
hkJ/kg_da
ρkg/m³
T_dew°C
AHg/m³
ṁ_exhaustkg/s
🔄Crossflow Plate HEX — ε-NTU Method ASHRAE HoF 2021 Ch.26 Eq.26.56
ε_s = 1 − exp[(NTU^0.22/C_r) · (exp(−C_r·NTU^0.78) − 1)]
C_r = C_min/C_max | T₂ = T₁ + ε_s·(T₃−T₁) | T₄ = T₃ − ε_s·C_r·(T₃−T₁)
NTU=— | C_r=— | ε_s=—%
📖 ASHRAE HoF 2021 Ch.26 Eq.26.56 + ASHRAE 90.1-2022 Table 6.5.6.1
☀ Summer Mode
T₁ OA inlet°C
T₃ Exhaust inlet°C
C_r
NTU
ε_s calculated%
T₂ OA leaving → coil°C
T₄ Exhaust leaving°C
Q_s recoveredkW
ΔP supplyPa
❄ Winter Mode
T₁ OA inlet°C
T₃ Exhaust inlet°C
C_r
NTU
ε_s calculated%
T₂ OA leaving → coil°C
T₄ Exhaust leaving°C
Q_s recoveredkW
ΔP exhaustPa
ASHRAE 90.1-2022 CZ4A — Summer ε_s ≥ 50%
ASHRAE 90.1-2022 CZ4A — Winter ε_s ≥ 50%
🧊Cooling Coil — Summer Design ASHRAE Fund. 2021, Ch.18
Q_s=ṁ·1.006·ΔT·1000 Q_l=ṁ·ΔW·2501·1000 Q_tot=Q_s+Q_l [W]
V_chw=Q[kW]·1000/(4186·ΔT_chw) [L/s] | d=√(4V/(π·v_w))·1000 [mm]
T_in=— (from HEX) | Q_s=— | Q_l=—
📖 ASHRAE Fund. 2021 Ch.18 | h_fg=2501 kJ/kg | cp,w=4186 J/(kg·K)
🧊 Cooling Loads
T_in (from HEX)°C
Q_sensiblekW
Q_latentkW
Q_totalkW
SHR
CondensateL/h
Face Area
🚿 CHW Piping
ΔT CHW°C
V_chwm³/h
Pipe IDmm
Nominal DN
🔥Heating Coil — Winter Design ASHRAE Fund. 2021, Ch.18
Q_heat = ṁ · 1.006 · (T_out − T_in) · 1000 [W] | V_hw = Q·1000/(4186·ΔT) [L/s]
T_in=— (HEX winter) | Q=—
📖 ASHRAE Fund. 2021 Ch.18
🔥 Heating Loads
T_in (from HEX)°C
Q_heatkW
Electric equivalentkW
♨ HW Piping
ΔT HW°C
V_hwm³/h
Pipe IDmm
Nominal DN
Fan Sizing & Performance Curves ASHRAE 90.1-2022 §6.5.3
P_shaft = V·ΔP/η_fan [W] | P_motor = P_shaft/η_motor | SFP = P_motor/V_m3h ≤ 2.5
📖 ASHRAE 90.1-2022 §6.5.3.1 | Motor IE3 (EN 60034-30)
⬆ Supply Fan
Flowm³/h
Static PressurePa
P_shaftW
P_motorkW
BHPhp
SFPW·s/m³
ASHRAE 90.1 SFP ≤ 2.5
⬇ Exhaust Fan
Flowm³/h
Static PressurePa
P_shaftW
P_motorkW
BHPhp
SFPW·s/m³
ASHRAE 90.1 SFP ≤ 2.5
⬆ Supply Fan Characteristic Curve
⬇ Exhaust Fan Characteristic Curve
🫧Filter Sizing ISO 16890 / ASHRAE 52.2 / EN 1822
G4 Pre-filter ISO Coarse 60–80% ASHRAE MERV 7-8 ΔP clean: 40 Pa Replace: 200 Pa Qty: pcs F7 Bag Filter ISO ePM1 ≥55% ASHRAE MERV 13 ΔP clean: 75 Pa Replace: 350 Pa Qty: pcs H14 HEPA EN 1822 — 99.995% Cleanroom / Medical ΔP clean: 250 Pa Replace: 600 Pa Qty: pcs G2 Exhaust ISO Coarse <60% Return air pre-filter ΔP clean: 20 Pa Replace: 100 Pa Qty: pcs → Supply Flow → ← Return Flow ←
Supply Filter Train — G4 → F7 → H14(opt.)
G4 Supply Qtypcs
F7 Supply Qtypcs
H14 HEPA (opt.)pcs
ΔP G4+F7 (clean)Pa
Exhaust Filter Train — G2 → G4
G2 Exhaust Qtypcs
G4 Exhaust Qtypcs
📄Engineering Summary Report ASHRAE Compliant Design
AHU Engineering Report
Location · Engineer · Date
💨 Airflow
Supplym³/h
Exhaustm³/h
Outdoor Airm³/h
ASHRAE 62.1 Minm³/h
🔄 HEX
ε_s summer%
ε_s winter%
Q recovered (S)kW
ASHRAE 90.1
🧊 Cooling
Q_totalkW
SHR
CHW Flowm³/h
CHW Pipe DN
🔥 Heating
Q_heatkW
HW Flowm³/h
HW Pipe DN
⚙ Fans
Supply fankW
Exhaust fankW
Total powerkW
ASHRAE 90.1 SFP
✅ Compliance
ASHRAE 62.1 OA
90.1 HEX ε_s
90.1 Fan SFP
References: ASHRAE Fundamentals Handbook 2021 Ch.1 (Psychrometrics) · ASHRAE HoF 2021 Ch.26 (Heat Exchangers, ε-NTU Eq.26.56) · ASHRAE 90.1-2022 §6.5.3 (Fan SFP) · §6.5.6 Table 6.5.6.1 (Energy Recovery CZ4) · ASHRAE 62.1-2022 §6.2.2 (Ventilation Rate Procedure) · ISO 16890-1:2016 (Air Filters) · EN 1822-1:2019 (HEPA) · Buck (1981) Pws equation