Project Information
General▾
Outdoor Design Conditions
ASHRAE 169-2021 Climate Data▾
P_atm = 101.325 · (1 − 2.25577×10⁻⁵ · z)^5.2559 [kPa]
→ z = 500 m → P = — kPa
📖 ASHRAE Fund. 2021 Ch.1 Eq.3
☀ Summer Design — 1% Exceedance
❄ Winter Design — 99.6% Exceedance
☀ Summer OA — Auto Calc
| P_atm | — | kPa |
| Dew Point T_d | — | °C |
❄ Winter OA — Auto Calc
| P_atm | — | kPa |
| Dew Point T_d | — | °C |
Indoor Design Conditions
ASHRAE 55-2020 / 62.1-2022▾
☀ Summer Set-Point
❄ Winter Set-Point
Airflow — Ventilation Rate Procedure
ASHRAE 62.1-2022 §6.2▾
V_bz = R_p·P_z + R_a·A_z [L/s] → V_oa,min = V_bz/1000·3600 [m³/h]
→ V_bz = —
📖 ASHRAE 62.1-2022 §6.2.2 Table 6-1
ASHRAE 62.1 OA Adequacy — V_bz = — m³/h
—
AHU System Schematic
System Overview▾
Air flow path: Outdoor Air → Filters → Crossflow HEX → Coils → Supply Fan → Supply Air
Return path: Exhaust Air → Crossflow HEX → Exhaust Fan → Outside
Psychrometric Analysis
ASHRAE Fund. 2021, Ch.1▾
P_ws = 0.61078·exp(17.269T/(237.3+T)) [kPa]
Buck 1981 — Summer: — | Winter: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.6
W = 0.621945·φ·P_ws / (P − φ·P_ws) [kg/kg]
Summer: — | Winter: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.20
h = 1.006·T + W·(2501 + 1.86·T) [kJ/kg_da]
Summer: — | Winter: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.32
ρ = 1/v v = 0.287055·(T+273)·(1+1.608W)/P
Summer ρ: — | Winter ρ: —
📖 ASHRAE Fund. 2021 Ch.1 Eq.28
📊 Psychrometric Chart (SI) — State Points & Processes
P_site = — kPa
① OA Summer
② OA Winter
③ After HEX (Summer)
④ After HEX (Winter)
⑤ Supply Air / After Coil
⑥ Room / Exhaust
☀ Summer — Outdoor Air
| T_db | — | °C |
| P_ws | — | kPa |
| W | — | kg/kg_da |
| h | — | kJ/kg_da |
| ρ | — | kg/m³ |
| T_dew | — | °C |
| AH | — | g/m³ |
| ṁ_supply | — | kg/s |
❄ Winter — Outdoor Air
| T_db | — | °C |
| P_ws | — | kPa |
| W | — | kg/kg_da |
| h | — | kJ/kg_da |
| ρ | — | kg/m³ |
| T_dew | — | °C |
| AH | — | g/m³ |
| ṁ_exhaust | — | kg/s |
Crossflow Plate HEX — ε-NTU Method
ASHRAE HoF 2021 Ch.26 Eq.26.56▾
ε_s = 1 − exp[(NTU^0.22/C_r) · (exp(−C_r·NTU^0.78) − 1)]
C_r = C_min/C_max | T₂ = T₁ + ε_s·(T₃−T₁) | T₄ = T₃ − ε_s·C_r·(T₃−T₁)
NTU=— | C_r=— | ε_s=—%
📖 ASHRAE HoF 2021 Ch.26 Eq.26.56 + ASHRAE 90.1-2022 Table 6.5.6.1
☀ Summer Mode
| T₁ OA inlet | — | °C |
| T₃ Exhaust inlet | — | °C |
| C_r | — | — |
| NTU | — | — |
| ε_s calculated | — | % |
| T₂ OA leaving → coil | — | °C |
| T₄ Exhaust leaving | — | °C |
| Q_s recovered | — | kW |
| ΔP supply | — | Pa |
❄ Winter Mode
| T₁ OA inlet | — | °C |
| T₃ Exhaust inlet | — | °C |
| C_r | — | — |
| NTU | — | — |
| ε_s calculated | — | % |
| T₂ OA leaving → coil | — | °C |
| T₄ Exhaust leaving | — | °C |
| Q_s recovered | — | kW |
| ΔP exhaust | — | Pa |
ASHRAE 90.1-2022 CZ4A — Summer ε_s ≥ 50%
—
ASHRAE 90.1-2022 CZ4A — Winter ε_s ≥ 50%
—
Cooling Coil — Summer Design
ASHRAE Fund. 2021, Ch.18▾
Q_s=ṁ·1.006·ΔT·1000 Q_l=ṁ·ΔW·2501·1000 Q_tot=Q_s+Q_l [W]
V_chw=Q[kW]·1000/(4186·ΔT_chw) [L/s] | d=√(4V/(π·v_w))·1000 [mm]
T_in=— (from HEX) | Q_s=— | Q_l=—
📖 ASHRAE Fund. 2021 Ch.18 | h_fg=2501 kJ/kg | cp,w=4186 J/(kg·K)
🧊 Cooling Loads
| T_in (from HEX) | — | °C |
| Q_sensible | — | kW |
| Q_latent | — | kW |
| Q_total | — | kW |
| SHR | — | — |
| Condensate | — | L/h |
| Face Area | — | m² |
🚿 CHW Piping
| ΔT CHW | — | °C |
| V_chw | — | m³/h |
| Pipe ID | — | mm |
| Nominal DN | — |
Heating Coil — Winter Design
ASHRAE Fund. 2021, Ch.18▾
Q_heat = ṁ · 1.006 · (T_out − T_in) · 1000 [W] | V_hw = Q·1000/(4186·ΔT) [L/s]
T_in=— (HEX winter) | Q=—
📖 ASHRAE Fund. 2021 Ch.18
🔥 Heating Loads
| T_in (from HEX) | — | °C |
| Q_heat | — | kW |
| Electric equivalent | — | kW |
♨ HW Piping
| ΔT HW | — | °C |
| V_hw | — | m³/h |
| Pipe ID | — | mm |
| Nominal DN | — |
Fan Sizing & Performance Curves
ASHRAE 90.1-2022 §6.5.3▾
P_shaft = V·ΔP/η_fan [W] | P_motor = P_shaft/η_motor | SFP = P_motor/V_m3h ≤ 2.5
📖 ASHRAE 90.1-2022 §6.5.3.1 | Motor IE3 (EN 60034-30)
⬆ Supply Fan
| Flow | — | m³/h |
| Static Pressure | — | Pa |
| P_shaft | — | W |
| P_motor | — | kW |
| BHP | — | hp |
| SFP | — | W·s/m³ |
ASHRAE 90.1 SFP ≤ 2.5
—
⬇ Exhaust Fan
| Flow | — | m³/h |
| Static Pressure | — | Pa |
| P_shaft | — | W |
| P_motor | — | kW |
| BHP | — | hp |
| SFP | — | W·s/m³ |
ASHRAE 90.1 SFP ≤ 2.5
—
⬆ Supply Fan Characteristic Curve
⬇ Exhaust Fan Characteristic Curve
Filter Sizing
ISO 16890 / ASHRAE 52.2 / EN 1822▾
Supply Filter Train — G4 → F7 → H14(opt.)
| G4 Supply Qty | — | pcs |
| F7 Supply Qty | — | pcs |
| H14 HEPA (opt.) | — | pcs |
| ΔP G4+F7 (clean) | — | Pa |
Exhaust Filter Train — G2 → G4
| G2 Exhaust Qty | — | pcs |
| G4 Exhaust Qty | — | pcs |
Engineering Summary Report
ASHRAE Compliant Design▾
💨 Airflow
| Supply | — | m³/h |
| Exhaust | — | m³/h |
| Outdoor Air | — | m³/h |
| ASHRAE 62.1 Min | — | m³/h |
🔄 HEX
| ε_s summer | — | % |
| ε_s winter | — | % |
| Q recovered (S) | — | kW |
| ASHRAE 90.1 | — |
🧊 Cooling
| Q_total | — | kW |
| SHR | — | — |
| CHW Flow | — | m³/h |
| CHW Pipe DN | — |
🔥 Heating
| Q_heat | — | kW |
| HW Flow | — | m³/h |
| HW Pipe DN | — |
⚙ Fans
| Supply fan | — | kW |
| Exhaust fan | — | kW |
| Total power | — | kW |
| ASHRAE 90.1 SFP | — |
✅ Compliance
| ASHRAE 62.1 OA | — | |
| 90.1 HEX ε_s | — | |
| 90.1 Fan SFP | — |
References:
ASHRAE Fundamentals Handbook 2021 Ch.1 (Psychrometrics) ·
ASHRAE HoF 2021 Ch.26 (Heat Exchangers, ε-NTU Eq.26.56) ·
ASHRAE 90.1-2022 §6.5.3 (Fan SFP) · §6.5.6 Table 6.5.6.1 (Energy Recovery CZ4) ·
ASHRAE 62.1-2022 §6.2.2 (Ventilation Rate Procedure) ·
ISO 16890-1:2016 (Air Filters) · EN 1822-1:2019 (HEPA) · Buck (1981) Pws equation